16AYC10B產(chǎn)品概述
The AYC Series filters are designed for 3-phase, four-wire noisy industrial wiring (WYE) applications such as frequency converters. The series offers filtering up to 180 amps maximum and meets EMC standards: EN55011, EN133200 and UL 1283. Maximum Leakage Current (Line-to-Ground): (16 A) 62, (25/36 A) 68, (63/80/110 A) 74 mA @ 120 VAC, 60 Hz; (16 A) 106, (25/36 A) 118, (63 A) 128, (80/110 A) 129 mA @ 250 VAC, 50 Hz. Hipot Rating (1 minute): Line-to-Ground — 1850 VDC; Line-to-Line — 1850 VDC; Line-to-Neutral — 1450 VDC. Operating Frequency: 50/60 Hz. Maximum Operating Voltage: 480 VAC.